Print Report
Off-Grid Solar Design Report
Project Location: Custom Point (Lat: 46.227807, Lon: -62.984737)
1. Design Basis (Critical Design Month)
Critical Month: December
Daily Load:
7.67 kWh/day
Design Insolation (PSH): 2.23 Hours
2. Inverter Sizing
Total AC Continuous Power:
4.16 kW
Total AC Surge Peak:
4.16 kW
Recommended Inverter Size:
5.0 kW
Pure Sine Wave
Safety Margin: 20%
Efficiency Setting: 93%
3. Battery Bank
Selected Model: Rolls 12 FS 185-HC
System Voltage: 48.0 V
Autonomy: 4 Days
Configuration:
4 Series × 5 Parallel = 20 Units
Total Storage Capacity: 43.44 kWh
4. PV Array
Selected Panel: LONGi LS54-410M-B
Configuration:
2 Series × 7 Parallel = 14 Panels
Total Array Power:
5.74 kW
Controller Requirement: MPPT (Max V > 150.0V)