Off-Grid Solar Design Report

Project Location: 300 Kent St, Charlottetown, PE C1A 4Z1, Canada (Lat: 46.240216, Lon: -63.121025)

1. Design Basis (Critical Design Month)

Critical Month: December
Daily Load: 6.6 kWh/day
Design Insolation (PSH): 1.68 Hours

2. Inverter Sizing

Total AC Continuous Power: 3.15 kW
Total AC Surge Peak: 3.15 kW
Recommended Inverter Size: 4.0 kW Pure Sine Wave
Safety Margin: 20%
Efficiency Setting: 93%

3. Battery Bank

Selected Model: Rolls 12 FS 185-HC
System Voltage: 48.0 V
Autonomy: 3 Days
Configuration: 4 Series × 3 Parallel = 12 Units
Total Storage Capacity: 26.06 kWh

4. PV Array

Selected Panel: LONGi LS54-410M-B
Configuration: 2 Series × 8 Parallel = 16 Panels
Total Array Power: 6.56 kW
Controller Requirement: MPPT (Max V > 150.0V)